Note
How to build and load a custom Niagara 4 module
Software Manager will accept a jar built from an empty directory without checking whether it does anything. Whether it installs and whether it works are two separate questions, and almost everything that decides them sits outside the dialog that says "Success."
- Module development
- Build tooling
- Deployment
What a module is on disk
A Niagara module is a signed jar with one extra file. Open one up and next
to the compiled classes and the usual jarsigner output
(META-INF/MANIFEST.MF, META-INF/NIAGARA4.SF,
META-INF/NIAGARA4.RSA) there is META-INF/module.xml
— the one part of the jar that is Niagara-specific, and the file the
station reads before it trusts anything else inside. Alongside it:
module.palette (what Workbench's palette side shows), a
<name>-rt.lexicon for translatable strings, and, for a
browser-facing module, an rc/ folder holding the
.js, .css and images the browser loads directly.
Nothing in the jar is obfuscated — javap, jdeps,
plain unzip and any decompiler all work on it directly.
A module also declares a runtime profile, both in its own
name and in module.xml's runtimeProfile
attribute: -rt runs inside the station itself,
-wb runs only inside Workbench, -ux is the one
that reaches an operator's ordinary browser. One piece of functionality
is often several jars sharing a logical name —
acmeTools-rt.jar, acmeTools-wb.jar,
acmeTools-ux.jar — each with its own module.xml,
targeting a different classpath at a different end of the wire. In a full
4.15 install, of roughly 750 shipped modules a little over half are
-rt, most of the rest -wb, and only a small
slice -ux — the profile that actually reaches a browser, and
the one a typical PX-facing widget module is.
Two ways to build one
There are two workable routes, and only one needs anything beyond a Niagara install already on disk.
Tridium ships its own Gradle-based build system inside every install, as a
flat Maven repository, with worked example projects for a driver, a
type-extension module, and a signing pipeline. It needs Gradle 7.6, a
full JDK (the one bundled inside a Niagara install is trimmed down and
drops the jar-packaging tools, so a separate system JDK 8 has to supply
jar and jarsigner), a Gradle plugin version
that actually matches the install you point it at, and — for a
-ux target only — Node tooling on PATH for its
grunt/yarn step. Type declarations for each profile live in their own
module-include.xml — one file per profile subproject sharing
a logical module name — folded into that profile's own
module.xml when the build runs. It is the fuller
build: it drives the @NiagaraType annotation processor,
which reads an annotation on a Java class and generates both the
Type/getType() boilerplate and the matching
<type> entry, so neither is written by hand. Signing
here is automatic too, but by a throwaway self-signed key generated on
first use — a development convenience, not a route to a shippable
module.
The other route needs no SDK and no licence: a plain javac
against the jars already in the install's own modules
directory, followed by a hand-built zip. This works by giving up the
annotation processor and writing its output by hand — not much of a
loss, since a browser-facing widget is typically a
BSingleton implementing BIJavaScript, and the
two methods the processor would otherwise generate are only a few
lines:
public static final Type TYPE = Sys.loadType(BAcmeWidget.class);
public Type getType() { return TYPE; }
private static final JsInfo jsInfo =
JsInfo.make(BOrd.make("module://acmeTools/rc/AcmeWidget.js"));
public JsInfo getJsInfo(Context cx) { return jsInfo; }
The matching <type> entry in module.xml is
written by hand alongside it, one line per class. Because these classes
only touch a handful of 4.0-era API
(javax.baja.sys.BSingleton,
javax.baja.web.BIFormFactorCompact/BIOffline,
javax.baja.web.js.BIJavaScript/JsInfo), the same
source compiles unchanged against whichever install javac is
pointed at, from a current 4.15 install back to 4.14 — Niagara 4 is Java 8
throughout. What a built jar actually asks the running station for at
load time is checkable rather than assumed: walk the constant pool of the
compiled classes, list every external framework method referenced, and
compare that against the API the oldest target actually has.
The bare minimum module.xml
Everything the station checks at install time is in one file. A minimal
-ux example, trimmed to the parts that matter:
<module name="acmeTools-ux" moduleName="acmeTools" runtimeProfile="ux"
vendor="Acme" vendorVersion="1.0.0" bajaVersion="0"
preferredSymbol="ac" nre="true" autoload="true" installable="true">
<dependencies>
<dependency name="baja" vendor="Tridium" vendorVersion="4.14"/>
<dependency name="js-ux" vendor="Tridium" vendorVersion="4.14"/>
</dependencies>
<types>
<type name="AcmeWidget" class="com.example.acmeTools.ux.BAcmeWidget"/>
</types>
</module>
Two details here catch people moving a module between hosts. First,
moduleName — not the jar's filename — is what an ORD or a PX
<import> resolves against, and Tridium's own shipped
modules aren't consistent about whether name or
class comes first inside a <type> element,
so parsing the file with a regex instead of a real XML parser eventually
gets it wrong. Second, the vendorVersion on each
<dependency> is a floor, not a pin — get that wrong and
a module that compiles cleanly is refused outright by an older station.
That distinction, and how to make the stamp a build argument instead of
an accident of the build machine, is its own note:
which Niagara version to
stamp a module for.
Signing, briefly
An unsigned jar installs on nothing running the default verification
mode — 4.15 documents medium, which requires a certificate
the target host already trusts. Self-signed is fine, but only once that
certificate is imported into that host's trust store; the same jar can
install cleanly on one host and be refused on the next with no change to
the file at all. What each mode actually checks, and why it cannot be
relaxed from a launch argument, is covered elsewhere:
Niagara module signing: what a
station checks. Worth repeating here: sign the version you are
actually going to ship, not the throwaway dev-loop key a build tool
generates by default.
Getting it onto a station
For a JACE, there is one supported way in: Platform → Software Manager,
pointed at the jar (or a distribution file built from it) over the
platform connection — not a jar copied into a directory by hand. A JACE
doesn't hand you a filesystem to engineer against the way a PC install's
own modules directory does during the SDK-less dev loop
above; Software Manager is what actually places the file, rebuilds the
module registry, and triggers whatever restart is needed. A jar that
compiles, is stamped correctly and is signed correctly, but was never
pushed through that path, is not installed anywhere — whatever the build
log says.
The three errors that actually mean something
Software Manager's own dialog isn't a diagnostic tool — it reports success or a short failure line, and the same line can cover more than one root cause. In practice, almost everything reduces to three.
| What it says | What it means |
|---|---|
| Dependency error naming a version | The module's declared floor is higher than the station's own version. Nothing in the code is wrong — rebuild with the stamp set to the station's actual version, not whatever version the build machine happens to have installed. |
| Unsigned or untrusted module | The jar's signing certificate is not in this host's trust store. The question is never "is it signed" — it's "does this particular host trust this particular certificate." |
| Class not found, after a successful install | The type resolved at install time, but a class it depends on lives
in a different runtime profile than the one that tried to load it
— a -ux view referencing a type that only exists on
the -rt/-wb side, or a type declared in
the wrong profile's module-include.xml. It installs,
then fails the first time something tries to instantiate it. |
None of these three is a reason to start guessing at the code — all three are checkable directly, against the stamp, the host's trust store, and the profile that was supposed to carry the failing class. See custom Niagara modules & drivers for help getting one built and shipped.
Sources
Where this is written down
- The jarsigner Command, JDK 25 tool specification — The tool that does the signing, and what a station's verification is actually checking when it accepts or refuses the jar
Related
Where this comes up in the work
Custom modules & drivers
Bespoke Niagara rt, wb and ux modules and drivers written against the Baja API: pure Java, signed, and stamped to install across a mixed estate.
More notes
Other things worth writing down
Which Niagara version to stamp a module for
A module's declared dependency version is a floor, not a pin. Build against the newest SDK you have and stamp for the oldest station it has to load on.
- Module development
- Mixed estates
- Build tooling
A link check that runs before a visitor finds the 404
A link check over your own built output, in CI: the four classes of break it finds, and why it works locally and it worked last deploy both miss them.
- Deployment
- Front end
- Testing
What a station checks before loading a module
Niagara's four verification-mode values, what each demands of your certificate, and the permissions that force a signature check even in low mode.
- Module signing
- Certificates
- Deployment