Note
What happens to third-party modules moving from N4 to N5
A migration can be refused before it starts, over one forgotten module — or load a signed module and reject an unsigned one right next to it. What breaks, in the order it breaks, sourced from Tridium's own transfer FAQ and a Platinum distributor's own words.
- Migration
- Estate management
- Module development
The failure that lands with no warning
An N4-to-N5 migration can be refused outright, and the reason is rarely the station itself. It is one module — usually a small one, usually installed years ago by someone who has since left — that the vendor never built for the new runtime. Tridium's own migration tooling checks for this, and can refuse to proceed.
This is worth knowing before a migration date goes on a calendar, not after.
What the distributor's own FAQ requires
One Sightsolutions, a Tridium Platinum distributor, puts it plainly in their N5 FAQ:
"Prior to executing the migration, you will need to identify any 3rd party modules (e.g. software not developed by Tridium) installed in the station and confirm whether an N5 version is available. If not, then the process may fail to execute."
Read that as a prerequisite, not a warning. The inventory has to happen before the migration is attempted, because the migrator's behaviour when it hits an unsupported module is to stop, not to skip it and continue.
A module with an N5 build is not automatically safe either
Niagara 5 moves the runtime off Java 8 — Tridium's current FAQ says to Java 25,
earlier partner material said 21 — and removes
SecurityManager entirely. One consequence of that removal is
that a valid signature stops being a recommendation and becomes
mandatory, with no grace period. An unsigned module, a self-signed one
outside your trust store, or one whose signing certificate has lapsed,
will not load — independent of whether the code itself has been ported.
So two separate questions need separate answers for every third-party module in a station: does an N5 build exist at all, and if it does, is it validly signed for the host it is going to load on. A module can clear the first test and still fail the second.
Licences do not travel with the software
Tridium's own JACE 8000-to-9000 licence transfer FAQ states that any third-party software options on JACE 8000 licences are moved to the customer's stock during the migration process. In practice that means the licence is detached from the host during the transfer, not carried forward automatically. Each third-party vendor then has to re-issue against the new Host ID before that feature runs again — a step that depends entirely on the vendor still being reachable and willing to do it.
The same stock-transfer mechanism applies to Tridium's own licensed options that have no JACE-9000 equivalent: the capability is not blocked, it is simply gone, because there is nothing on the new platform to re-attach the licence to.
Graphics: what actually carries over
The migrator's Px handling is qualified, not blanket. The distributor's FAQ describes it as covering Px "for standard Niagara Px capabilities" — standard sheets and standard bindings move across cleanly. What does not move across is the theme: Niagara 5 ships new navigation, layout and themes, and the N4 Zebra and Lucid themes are not carried forward. Any graphics built or styled against those themes, or any custom bajaux widget skinned to match them, needs a visual review after migration — not an assumption that it will look the same.
None of this is a 2026 deadline
It is worth being precise about the dates, because the framing around this release tends to compress them. 31 October 2026 is the cut-off for a licence-transfer discount; after it, the JACE 8000-to-9000 transfer costs full price instead of just the transfer fee, and nothing about a running station changes on that date. Niagara 4 itself reaches end of life in Q3 2028, and Niagara 4.15 — the last N4 release — is a long-term-support version supported through that date, on both JACE-8000 and JACE-9000 hardware. There is no cliff in 2026. There is a widening gap between stations that know what will survive the move and stations that do not, and that gap gets more expensive to close the longer it is left.
What to build before the date gets picked
The useful output is a list, not an impression: every third-party module in the station, its vendor, whether an N5 build exists, and whether its current signature is valid and trusted. For anything without a clear yes on both, decide early whether the vendor is going to do the work, whether the module can be replaced, or whether it needs rebuilding from its observed behaviour because the original vendor is no longer reachable. That last case is more common on older estates than most people expect, and it is the one that turns a software question into a scheduling one. When a third-party module's vendor no longer exists works through what is left to do once that is the situation you are in.
For the audit and porting work itself, see Niagara 5 migration.
Sources
Where this is written down
- JEP 486: Permanently Disable the Security Manager — The JDK change behind "removes SecurityManager entirely": enabling one is now an error the JVM refuses to start on, delivered in JDK 24, so the Java 25 an N5 runtime sits on inherits the change
Related
Where this comes up in the work
Niagara 5 migration
Niagara 5 readiness audits and migration, including JACE 8000 to JACE 9000: which third-party modules survive the new runtime and mandatory signing.
Custom modules & drivers
Bespoke Niagara rt, wb and ux modules and drivers written against the Baja API: pure Java, signed, and stamped to install across a mixed estate.
More notes
Other things worth writing down
What a static Niagara 5 module scan actually finds
Reading a module's bytecode against Java 25 gives a per-module answer. What it finds, what it cannot tell you, and the false alarms it avoids.
- Migration
- Module development
- Estate management
What actually blocks an AX to N4 migration
A station cannot migrate until every module it uses has been refactored for Niagara 4 — and licences, users and permissions all change shape on the way.
- Migration
- Estate management
- Module development
When a third-party module's vendor no longer exists
The Marketplace storefront is gone and vendors are winding down. How to list which third-party modules a station depends on, and who owns each.
- Migration
- Estate management
- Drivers
Next step
Tell us the version, the hardware, and what it has to do.
You will get a written scope and a fixed price against it. If the honest answer is that you do not need us, you will get that instead.